Before the Building Practitioners Board 
BPB Complaint No. C2-01942 
Licensed Building Practitioner: 
Mark Hanson (the Respondent) 
Licence Number: 
BP 130700 
Licence(s) Held: 
Carpentry 
 
 
Decision of the Board in Respect of the Conduct of a Licensed Building Practitioner 
Under section 315 of the Building Act 2004 
 
 
Complaint or Board Inquiry 
Complaint 
Hearing Location 
Wellington 
Hearing Type: 
In Person 
Hearing Date: 
23 January 2019 
Decision Date: 
11 February 2019  
Board Members Present: 
 
Richard Merrifield, LBP, Carpentry Site AOP 2 (Presiding)  
Mel Orange, Legal Member 
David Fabish, LBP, Carpentry Site AOP 2  
Robin Dunlop, Retired Professional Engineer 
 
Appearances: 
 
Alan Knowsley, Solicitor, Rainey Collings for the Respondent  
Procedure: 
The matter was considered by the Building Practitioners Board (the Board) under the 
provisions of Part 4 of the Building Act 2004 (the Act), the Building Practitioners (Complaints 
and Disciplinary Procedures) Regulations 2008 (the Complaints Regulations) and the Board’s 
Complaints and Inquiry Procedures.  
Board Decision: 
The Respondent has not committed a disciplinary offence.  
 
 

link to page 2 link to page 2 link to page 2 link to page 5 C2-01942 
Contents 
Introduction ............................................................................................................................................ 2 
Function of Disciplinary Action .............................................................................................................. 2 
Evidence .................................................................................................................................................. 2 
Board’s Conclusion and Reasoning ........................................................................................................ 5 
 
Introduction 
[1] 

The hearing resulted from a complaint into the conduct of the Respondent and a 
Board resolution under regulation 10 of the Complaints Regulations1 to hold a 
hearing in relation to building work at [Omitted]. The alleged disciplinary offence the 
Board resolved to investigate was that the Respondent carried out or supervised 
building work or building inspection work in a negligent or incompetent manner (s 
317(1)(b) of the Act). 
Function of Disciplinary Action 
[2] 
The common understanding of the purpose of professional discipline is to uphold the 
integrity of the profession. The focus is not punishment, but the protection of the 
public, the maintenance of public confidence and the enforcement of high standards 
of propriety and professional conduct. Those purposes were recently reiterated by 
the Supreme Court of the United Kingdom in R v Institute of Chartered Accountants 
in England and Wales
2 and in New Zealand in Dentice v Valuers Registration Board3. 
[3] 
Disciplinary action under the Act is not designed to redress issues or disputes 
between a complainant and a respondent.  In McLanahan and Tan v The New 
Zealand Registered Architects Board4
 Collins J. noted that: 
“… the disciplinary process does not exist to appease those who are dissatisfied 
… . The disciplinary process … exists to ensure professional standards are 
maintained in order to protect clients, the profession and the broader 
community.” 

[4] 
The Board can only inquire into “the conduct of a licensed building practitioner” with 
respect to the grounds for discipline set out in section 317 of the Act. It does not 
have any jurisdiction over contractual matters. 
Evidence 
[5] 
The Board must be satisfied on the balance of probabilities that the disciplinary 
offences alleged have been committed5. Under section 322 of the Act the Board has 
                                                           
1 The resolution was made following the Board’s consideration of a report prepared by the Registrar in 
accordance with the Complaints Regulations. 
2 R v Institute of Chartered Accountants in England and Wales [2011] UKSC 1, 19 January 2011. 
3 [1992] 1 NZLR 720 at p 724 
4 [2016] HZHC 2276 at para 164 
Z v Dental Complaints Assessment Committee [2009] 1 NZLR 1 


C2-01942 
relaxed rules of evidence which allow it to receive evidence that may not be 
admissible in a court of law.  
[6] 
The procedure the Board uses is inquisitorial, not adversarial. The Board examines 
the documentary evidence available to it prior to the hearing. The hearing is an 
opportunity for the Board, as the inquirer and decision maker, to call and question 
witnesses to further investigate aspects of the evidence and to take further evidence 
from key witnesses. The hearing is not a review of all of the available evidence.  
[7] 
In addition to the documentary evidence before the Board heard evidence at the 
hearing from: 
Mark Hanson 
Respondent 
[Omitted] 
Witness, Building Surveyor 
[Omitted]  
Witness for the Respondent  
[8] 
The Respondent was engaged to carry out building work in the interior of a Versatile 
barn to create a living space. A building consent was issued for the conversion but it 
only covered sanitary plumbing. The Respondent was aware that the Complainant 
would be using the shed to live in whilst constructing a main residence on the 
property.  
[9] 
The conversion had been designed by a licensed building practitioner with a design 
licence. The design and specification was provided to the Respondent. Framing for 
the living space was constructed inside of the Versatile metal framing. The internal 
framing was insulated. There were no points of load transfer other than within a 
storage space. No structural changes were made to the existing building.  
[10] 
The Complainants obtained a report from [Omitted] post its completion. The report 
set out various allegations as regards plywood linings including that: 
(a) 
the plywood sheets have been installed in a random method and there is no 
uniformity to the sheet layout; 
(b) 
most sheets have been installed with the grain of the plywood running 
vertically, however some sheets have been used with the grain running 
horizontally; 
(c) 
the plywood sheets have been butted together and there is no gap, as 
required, to allow for movement of the sheets; 
(d) 
some of the plywood sheets have pulled away from the framing; 
(e) 
the plywood sheets have been fixed to the studs with nail gun brads although 
the specification sheet states to use only flathead nails or screws; 
(f) 
there is evidence that the plywood has been glued to the framing, although 
this does not appear to be every stud; 


C2-01942 
(g) 
there is no uniformity to the spacing of the plywood fixings. (h) Some fixings 
are missing from the perimeter of the sheets. (i) Undersized fixings were used 
to fix the plywood to the framing; 
(h) 
the plywood used on the door frames has been patched at the base however 
full lengths should have been used; 
(i) 
there has been movement to the interior wall, which has caused the plywood 
linings to pop the fixings, split, and bulge outward; and  
(j) 
the timber framing was too wet when the linings were installed. There are no 
records of moisture content (MC) to the timber, as this was not part of the 
building consent requirements. However, wet timber causes movement as it 
dries. 
[11] 
The report also set out issues with doors that had been made by the Respondent 
from wet rough sawn timber including that gaps had formed from timber shrinkage 
and with the fixing of plywood sheets in a storage space that had been created 
above an internal ceiling. The report writer also expressed a concern over whether 
the structure could sustain the loads created by the storage area.  
[12] 
The Respondent provided a written response to the complaint. In it he noted a 
commercial dispute with the Complainant and that he had not been afforded the 
opportunity to rectify issues because of that dispute. He also submitted that the 
building work was not restricted building work.  
[13] 
At the hearing the Board heard evidence that the lifting of the plywood was the 
result of environmental factors in the internal livings space where there would have 
been extensive expansion and contraction of the sheets through moisture take up 
from living in and drying from an installed log burner. It was noted that gaps 
between plywood sheets would have been advisable but that this was not on the 
design and was not what the Complainant wanted. It was also noted sealing on both 
sides of the plywood would have been advisable but it had not been specified and 
that the Complainant was to undertake the sealing of the sheets. [Omitted] agreed 
that the moisture levels would have been less if the building was not lived in.  
[14] 
Reference was made by [Omitted] to a Carter Holt Harvey (CHH) non-structural ply 
specification and a copy of it was admitted into evidence. There was no specification 
for the actual ply supplied and installed. The Respondent stated that he was referred 
to the CCH specification which he did use. It contained minimal direction.  
[15] 
The Respondent gave evidence that he glued and nailed the plywood but that some 
incorrect fixing nails may have been used by accident. He produced an invoice which 
showed the purchase of the correct length fixings.  
[16] 
With regard to the storage area the Respondent gave evidence that the Complainant 
wanted the ply flooring to be temporarily fixed to allow for future access to the sub 
space for the possible install of services. He also gave evidence that the structure 


C2-01942 
over which the storage area was created was more than adequate for the loads to be 
created and that the design of it was more than was required under NZS 3604. 
[17] 
With regard to the doors that the Respondent built he stated that he gave the 
Complainant various options including kiln dried dressed timber but that rough sawn 
wet timber was chosen for aesthetic and cost reasons. He noted both he and the 
designer had not endorsed the use of wet rough sawn timber. The Respondent gave 
evidence that he screwed the timber boards used to allow for future adjustment.  
Board’s Conclusion and Reasoning 
[18] 
The Board has decided that the Respondent has not carried out or supervised 
building work or building inspection work in a negligent or incompetent manner (s 
317(1)(b) of the Act) and should not be disciplined. 
[19] 
There were two aspects the Board was considering in the context of negligence and 
incompetence. The first was whether a building consent was required for the 
building work undertaken. In this respect the Board was satisfied that what was 
undertaken came within the provisions of Schedule 1 of the Building Act in that it 
was exempt from the requirement to obtain a building consent. 
[20] 
The Respondent is cautioned, however, to take care in future with regard to the 
requirement for a building consent and to ensure that he carries out full enquiries to 
ensure one is not required prior to commencing the building work.  
[21] 
The second concern was with regard to the building work itself. In this respect the 
Board has decided that whilst the Respondent could have done better his conduct 
was not sufficiently serious enough to warrant a disciplinary outcome. In coming to 
its decision the Board has applied the following test.  
[22] 
Negligence and incompetence are not the same. In Beattie v Far North Council
Judge McElrea noted: 
[43] Section 317 of the Act uses the phrase "in a negligent or incompetent 
manner", so it is clear that those adjectives cannot be treated as synonymous. 

[23] 
Negligence is the departure by a licensed building practitioner, whilst carrying out or 
supervising building work, from an accepted standard of conduct. It is judged against 
those of the same class of licence as the person whose conduct is being inquired 
into. This is described as the Bolam7 test of negligence which has been adopted by 
the New Zealand Courts8. 
[24] 
Incompetence is a lack of ability, skill or knowledge to carry out or supervise building 
work to an acceptable standard. Beattie put it as “a demonstrated lack of the 
                                                           
6 Judge McElrea, DC Whangarei, CIV-2011-088-313 
Bolam v Friern Hospital Management Committee [1957] 1 WLR 582 
Martin v Director of Proceedings [2010] NZAR 333 (HC), F v Medical Practitioners Disciplinary Tribunal [2005] 
3 NZLR 774 (CA) 


C2-01942 
reasonably expected ability or skill level”. In Ali v Kumar and Others9 it was stated as 
“an inability to do the job”
[25] 
The New Zealand Courts have stated that assessment of negligence and/or 
incompetence in a disciplinary context is a two-stage test10. The first is for the Board 
to consider whether the practitioner has departed from the acceptable standard of 
conduct of a professional. The second is to consider whether the departure is 
significant enough to warrant a disciplinary sanction.  
[26] 
When considering what an acceptable standard is the Board must have reference to 
the conduct of other competent and responsible practitioners and the Board’s own 
assessment of what is appropriate conduct, bearing in mind the purpose of the Act11. 
The test is an objective one and in this respect it has been noted that the purpose of 
discipline is the protection of the public by the maintenance of professional 
standards and that this could not be met if, in every case, the Board was required to 
take into account subjective considerations relating to the practitioner12.  
[27] 
The Board notes that the purposes of the Act are: 

Purposes 
This Act has the following purposes: 
(a) 

to provide for the regulation of building work, the establishment of a 
licensing regime for building practitioners, and the setting of 
performance standards for buildings to ensure that— 
(i) 

people who use buildings can do so safely and without 
endangering their health; and 

(ii) 
buildings have attributes that contribute appropriately to the 
health, physical independence, and well-being of the people 
who use them; and 

(iii) 
people who use a building can escape from the building if it is 
on fire; and 

(iv) 
buildings are designed, constructed, and able to be used in 
ways that promote sustainable development: 

(b) 
to promote the accountability of owners, designers, builders, and 
building consent authorities who have responsibilities for ensuring 
that building work complies with the building code. 

[28] 
The Board also notes, as regards acceptable standards, that all building work must 
comply with the Building Code13 and be carried out in accordance with a building 
                                                           
9 Ali v Kumar and Others [2017] NZDC 23582 at [30] 
10 Martin v Director of Proceedings [2010] NZAR 333 (HC), F v Medical Practitioners Disciplinary Tribunal [2005] 
3 NZLR 774 (CA) 
11 Martin v Director of Proceedings [2010] NZAR 333 at p.33 
12 McKenzie v Medical Practitioners Disciplinary Tribunal [2004] NZAR 47 at p.71 
13 Section 17 of the Building Act 2004 



C2-01942 
consent14. As such, when considering what is and is not an acceptable standard, the 
Building Code and any building consent issued must be taken into account.  
[29] 
Turning to seriousness in Collie v Nursing Council of New Zealand15 the Court’s 
noted, as regards the threshold for disciplinary matters, that: 
[21] Negligence or malpractice may or may not be sufficient to constitute 
professional misconduct and the guide must be standards applicable by 
competent, ethical and responsible practitioners and there must be behaviour 
which falls seriously short of that which is to be considered acceptable and 
not mere inadvertent error, oversight or for that matter carelessness.
 
[30] 
When looking at the building work in question the Board’s main concern was with 
the installation of the plywood. The Board noted that environmental factors were 
the main contributing factor. Neither the designer nor the Respondent turned their 
mind to those factors. More care should have been taken by both and consideration 
given to how the materials would perform in the environment.  
[31] 
The Board also considered that the Respondent should have taken more care in the 
installation of the ply wood. Correct fixings should have been used throughout and 
the grain of the material installed should have been consistently matched.  
[32] 
The Board finds that neither of the above matters are serious enough to warrant a 
disciplinary outcome. In coming to this decision the Board has also noted the 
comments of the Court of Appeal in Pillai v Messiter (No 2)16: 
… the statutory test is not met by mere professional incompetence or by 
deficiencies in the practice of the profession. Something more is required. It 
includes a deliberate departure from accepted standards or such serious 
negligence as, although not deliberate, to portray indifference and an abuse. 

 
Signed and dated this 11th day of February 2019  
 