SMS Incident Report     F2398133
2/6
 20/10/2017 12:21:04
Notifications
Date
Time
Party Notified
16 Oct 2017
14:47:37
AREA SOUTH CANTERBURY PAGED RE 
16 Oct 2017
14:49:44
AREA SOUTH CANTERBURY MARTYN BENNETT ACKD PAGE
16 Oct 2017
15:03:26
AREA SOUTH CANTERBURY PAGED RE 
16 Oct 2017
15:07:07
AREA SOUTH CANTERBURY ACKD FURTHER UPDATE
16 Oct 2017
15:16:39
PAGED FI STH CANTERBURY BEVAN FINDLAY AND MURRAY CAIRNS
16 Oct 2017
15:19:18
RFOM SOUTH CANTERBURY (BEVAN FINDLAY ) ACL - TRANSFERED TO 
TIMA804
Message Log 
Time
Message
14:36:44
INC INFO: CEILING FIRE
14:36:47
** LOI search completed at 16/10/17 14:36:47
14:36:55
** Recommended unit TIMA804 for requirement PUMP (>1.1 km)
14:36:55
** Recommended unit WASH817 for requirement PUMP (>3.7 km)
14:37:11
THIS IS SECOND HAND INFO. FROM TIMARU STATION
14:37:22
FIRE IS BELIEVED OUT
14:37:37
Unit WASH817 [ K1 : PROCEEDING TO INCIDENT]
14:37:40
AL: PAGING ACK RECEIVED FROM STATION 3581 at 16/10/17 14:37:40
14:37:46
Unit TIMA804 [ K1 : PROCEEDING TO INCIDENT]
14:37:53
AL: PAGING ACK RECEIVED FROM STATION 3580 at 16/10/17 14:37:53
14:39:13
Unit TIMA804 [COMCEN COM : MESSAGE] FURTHER INFO PASSED
14:41:02
***
14:41:05
Unit TIMA804 [ K77 : NOTHING SHOWING]
14:41:37
T3 INCORRECT ATTEMPTS TO INPUT ADDRESS
14:43:50
Unit WASH817 [ K2 : IN ATTENDANCE AT INCIDENT]
14:44:49
Unit TIMA804 [ KC : UNIT CALLING]
14:45:28
Unit TIMA804 [ SITREP : ] SO NG, K11A 
 FOR ONE OF THE HOME
14:45:28
OWNERS
under the Official Information Act 1982
14:45:33
Unit TIMA804 [ K11A : AMBULANCE REQUIRED]
14:45:35
.
14:45:46
Unit TIMA804 [ KC : UNIT CALLING]
14:45:49
FIR2AMB CAN WE HAVE YOUR ATTENDANCE FOR ONE PATIENT WITH 
14:46:12
Unit TIMA804 [ SITREP : ] FIRE IN KITCHEN EXTRACTOR SYSTEM OOA
14:46:20
AMBO EVENT 0277-3-2017/10/16-FIR LINKED AT 16/10/2017 14:46:20
14:59:35
Unit TIMA804 [ KP : PRIORITY MESSAGE]
15:00:14
Unit TIMA804 [ KP : PRIORITY MESSAGE] AMB HAS 
Released 
15:00:14
Caution: The information contained in this report is subject to the provisions of the Official Information Act 1982 and the Privacy Act 1993. Neither the information nor the 
report should be released to any person outside NZ Fire and Emergency without prior approval

SMS Incident Report     F2398133
3/6
 20/10/2017 12:21:04
15:00:24
Unit TIMA804 [ K11A : AMBULANCE REQUIRED]
15:00:48
FIR2AMB AMB REQUIRED URGENTLY PERSON WITH 
15:00:48
15:03:37
Unit TIMA804 [COMCEN COM : MESSAGE] ETA FOR AMBO PASSED
15:06:06
Unit TIMA804 [ KC : UNIT CALLING]
15:06:57
Unit TIMA804 [ SITREP : ] 
 AND AMB IN ATTEND+
15:12:57
Unit TIMA804 [ KC : UNIT CALLING]
15:14:18
Unit TIMA804 [ K11F : FIRE SAFETY REQUIRED]
15:14:57
INC INFO: CEILING FIRE TOC 1436 TOA 1441
15:16:40
Unit WASH817 [ K22-1 : UNIT AVAILABLE FOR A FURTHER EVENT]
15:18:40
**
15:29:25
Unit FISTHCANT1 [ K1 : PROCEEDING TO INCIDENT]
15:30:31
Unit FISTHCANT1 [ K2 : IN ATTENDANCE AT INCIDENT]
15:52:08
Unit WASH817 [ K4 : ON RT INSIDE NORMAL TURNOUT AREA]
15:55:32
Unit TIMA804 [ KC : UNIT CALLING]
15:55:59
Unit TIMA804 [ STOP : MESSAGE] SCENE LEFT WITH FIRE SAFETY
15:56:17
Unit TIMA804 [ K4 : ON RT INSIDE NORMAL TURNOUT AREA]
16:04:48
Unit FISTHCANT1 [ K6 : ON TELEPAGER]
17:46:09
** Assigned Result Code: STRU, Detailed Event Type: 1100, Qualifier 1: Q1,
17:46:09
Qualifier 2:
Incident
CAD Number
F2398133
Incident Reporter
Craig Ng
Incident Controller
SO Ng
Distance Travelled (km)
4
Delay In Receiving Call
Property Details
Occupant
under the Official Information Act 1982
Building Owner
Rented property
General Property Use
Single house
Special Property Use
Single house
Purpose Group
Actions
Persons Reported Trapped
No
Evacuation Status
No evacuation
Released 
Action Prior 1
Bucket/Container of water, bucket pump
Caution: The information contained in this report is subject to the provisions of the Official Information Act 1982 and the Privacy Act 1993. Neither the information nor the 
report should be released to any person outside NZ Fire and Emergency without prior approval

SMS Incident Report     F2398133
4/6
 20/10/2017 12:21:04
Action Prior 2
No action taken by Civilian/Occupant/Passerby
Action Taken
Extinguishment and ventilation
Civilians
Civilians Rescued
0
Civilians Extricated
0
Civilians Assisted
2
Civilians Evacuated
Origin
Location
Kitchen, Cooking area
Level
Ground level
Equipment Used
Quantity
Equipment
0
Bucket pump or buckets of water - by Occupant/Passerby
1
First aid kit, including O2 units, surgical gloves 
1
Ladder
1
Thermal Imaging Camera
1
Salvage/ventilation: PPV, Fan
4
Equipment Involved
Equipment Involved
Year
Make
Turbo
Model
unsure
Fire
Arrival Condition
Out on arrival
Heat Source
Heat from electrical equipment: Defective or 
under the Official Information Act 1982
faulty
Termination Stage
Overheat
First Object Ignited
Electronic componentry
First Object Material
Plastics - not classified above
Second Object Ignited
Interior wall covering
Second Object Material
Gypsum board, Gib board, Elephant board
Indicated Cause
Other electrical failure
Certainty of Cause
Medium
Released 
Age of Person
Persons: 17 - 64 yrs
Ethnicity
Asian / Indian
Caution: The information contained in this report is subject to the provisions of the Official Information Act 1982 and the Privacy Act 1993. Neither the information nor the 
report should be released to any person outside NZ Fire and Emergency without prior approval

SMS Incident Report     F2398133
5/6
 20/10/2017 12:21:04
Gender
Female
FAIP Service Offered
No
FAIP Service Accepted
No
Alarms
Type of Alarm Initiating Call
Domestic Smoke Alarms
Performance of System
Detector not in room of origin - not classified above
Failure/Ineffectiveness of 
Detector not in room of origin
system
Number of sprinkler heads 
0
operated
Structure
Area of One Floor
100
Age of Building
1946 - 1969
Structural Frame Type
Brick, Blocks etc
Number of Floors
1
Number of Basements
0
Internal Wall Lining
Gypsum board (e.g. Gib board, Elephant board)
Ceiling Lining
Fibrous plaster
Material Generating Most Flame
Plastics - not classified above
Material Generating Most Smoke
Plastics - not classified above
Avenue of Flame Travel
Unknown
Avenue of Smoke Travel
No travel
Extent of Flame Damage
Confined to room of origin
Area of Flame Damage
5
Extent of Smoke Damage
Confined to room of origin
Area of Smoke Damage
10
Extent of Water Damage
No damage of this type
Area of Water Damage
0
Extent of Fire Control Damage
No damage of this type
Area of Fire Control Damage
0
under the Official Information Act 1982
Casualties
Casualty Number 1
Gender
Female
Age
35
Apparent Injury
Ethnicity
Asian / Indian
Released 
Severity of Injury
Caution: The information contained in this report is subject to the provisions of the Official Information Act 1982 and the Privacy Act 1993. Neither the information nor the 
report should be released to any person outside NZ Fire and Emergency without prior approval

SMS Incident Report     F2398133
6/6
20/10/2017 12:21:04
Bleeding
No
Action  by Fire FIghters
Provided basic first aid
Condition Before Injury
Awake, unimpaired
How Removed
Taken to hospital: Ambulance
Location at Ignition
Person in room or space of fire origin
Factor Preventing Escape
NOTHING preventing escape
Activity When Injured
Fire control attempt
Cause of Injury
Exposed to fire products
Victim Aware of Fire
Victim alerted by other than domestic smoke
Room Where Victim Found
Unable to classify
Location Where Victim Found
Unable to classify
Familiarity With Property
Unknown
Comments
10/17/2017 9:33:30 AM
Reporter Comments
On brigade arrival, 
 were still inside house. 
 was cooking. She 
turned the rangehood on and heard a bang, then the rangehood caught fire. She put it 
out with a pan of water. She received 
 while trying to remove the 
covering of rangehood. 
. And 
.
The make and model of the rangehood I am not 100%. It had the word Turbo on the 
front face and that was all.
Concerns about raising alarm and no evacuation of the house. We removed 
patient to outside for 1st aid.
Harcourts property manager received initial phone call from 
.
Fire Safety Craig Chambers attended. 