Further information about changes to standards included in Energy 
Safety Standards Update 
Electricity (Safety) Regulations 2010 (the ESR) 
EXTRACT: 
AS/NZS 3000:2018 Electrical instal ations (known as the Australian/New Zealand Wiring Rules). 
Including Amendments 1, 2 and 3 
We propose several modifications to this standard, which are noted in the table below along with the 
reasons for the change. 
In addition, we wil  continue our work with Standards New Zealand to insert these changes into the 
substantive standard through the normal standards amendment process. 
Suggested modification 
Reason for change 
Delete clauses 2.3.2.1.2(b) and 2.3.2.1.2(c) 
These two clauses prevent the switching and/or 
isolation of the neutral and earthing conductors. 
However, there needs to be an ability to switch the 
neutral and earth for EV charging, Terra Terra (TT), 
and Isolated Terra (IT) circuits, as well as when an 
installation is operated independent of the grid. 