This is an HTML version of an attachment to the Official Information request 'WorkSafe Advice to MBIE on Removal of Clauses 2.3.2.1.2 (b) & (c) of AS/NZS3000:2018'.
AS/NZS 3000:2007: Electrical instal ations 
AS/NZS 3000:2018
1 year transition with the 
1. Add wording following paragraph
(known as the Australian/New Zealand Wiring 
Electrical installations - 
immediate ability to use
(b)(ii) of clause 1.7.3 "Exemption:
Rules): including Amendments 1 and 2, 
Known as the 
Any appliance or fitting imported
subject to the following modifications:
Australian/New Zealand 
into NZ that forms part of a
1. In 4.5.2.3.2, change “warning sign shal  be
Wiring Rules - Inculding 
imported caravan, where the fitting
installed” to “warning sign shall be installed
Amendment 1, 
or appliance complies with the
or fitted in domestic installations but may be
Amendment 2, and 
exemption to clause  E4.3.4.1 of
omitted from all other installations”.
Amendment 3. with the 
AS/NZS 3001.2  can fol ow the
2. In 4.18.1(b) and (c), change “al  live (active
following modifications:
requiremnts of that clause."
and neutral) conductors” to “all active
conductors”.
The reason is so that a imported 
3. Add a new paragraph to 4.18.2: “In New
second hand caravan does not 
Zealand, only electrical equipment that is
have to remove a socketoutlett that 
directly associated with the gas supply may
is perminately pluged into a built in 
be installed in the hazardous areas of a
appliance - reducing compliance 
domestic instal ation, shown in figure 4.10.”
costs for the end user.
4. Replace 4.18.3 with “In New Zealand, only
electrical equipment (including metering
equipment) that is directly associated with
the gas supply may be instal ed in the
exclusion zones of a domestic installation in
figure 4.11.”
under the Official Information Act 1982
Released 

2. Change to: Remove reference  3. Delete clause 2.6.2.2.3(b) 
4. Delete 2.6.3.3.2 Exception 2, 
5. In clause 4.18.5 Reticulated  6. Amend clause 4.18.5 so 
to 2.3.2.1.2(b) and 2.3.2.1.2(c)
and replace it with:
Bul et point 2 – this exception is  lighter-than-air gas system, 
that the term "hazardous area" 
1982
no longer needed due to change  delete the words "lighter-than- has the same meaning as 
The reason for this is that there 
"Either type A in accordance 
in technology use.
air" 
"exclusion zone" and the title 
needs to be an ability to switch the  with IEC 61009.1 or IEC 
for Figure 4.20.
Act 
neutral and earth for EV charging,  61008.1
Considered MOE 
Reason: this would allow this 
TT, and IT circuits, as wel  as when  Or
clause to also apply to 
Reason: A hazardous area is 
an installation is operated 
Type F or Type  B in accordance 
reticulated LPG installations.
different to an exclusion zone. 
independent of the grid.
with IEC 62423." 
An exclusion zone does not 
allow any electrical equipmet 
Reason:
into the zone where as a 
This is to al ow the use of Type 
hazardous area, which does 
B and F RCDs
not exist in residential, requires 
special precaustion for eletrical 
Information  equipment as wel as a periodic 
inspection. We do not want to 
impose a periodic inspection 
on domestic premesis in this 
way.
Official 
the 
under 
Released 

7. Amend clause 4.18.2.3 so  8. In clause 8.3.10 paragraph 2 delete the  9. Remove the words "It is 
10. With the exception of  11. Clause 7.9.3 
that the term "hazardous area"  words "either by the operation of the 
recommended that the" from  clause 7.9.4
change title and all 
1982
has the same meening as 
integral test device, or".
clause 8.3.2.2
words in the clause to 
"exclusion zone" and the title 
remove the word 
for Figure 4.18
Then: add in new paragraph 5 after 
“domestic” 
Act 
paragraph 4: 
Reason:
Reason:
The function testing of the RCD is to 
So that the installer has to 
So that the requirments 
include trip time, as wel  as confirmation  keep records of testing due to  of clause 7.9.3 can apply  Reason: to clarify that 
that the functions that the RCD has are 
investigations that have 
to non comestic 
the clause applies in 
working, as wel  as confirmation that 
occurred have uncovered that  installations.
all installation rather 
protection against electric shock is 
electricians are not making 
than just domestic 
provided by which tripping is ensured for  records of testing meaning 
residual sinusoidal alternating current and  that they often don't 
residual pulsating direct current, as wel   remember what they tested.
Information 
as the presence of DC leakage, as wel  as 
constant DC where applipable.”
Delete note 4.
Official 
The reason for this is to ensure that RCDs 
are tested to ensure that they are working 
but are not deemed unsafe by Regulation 
the 
24 of the Electricity (Safety) Regulations 
due to the trip time.
under 
Released 

Add a clause number 
Change: 2.2.1.4 
Change clause 7.9 and 
Change clause 1.5.6.3: 
Delete clause 1.6.2(c)  Replace: 
7.9.3.4 "The 
appendix P to make al  Mode  At the end of paragraph 1 insert  note (b)
2.6.3.3.3 – All with “ 
1982
requirements in 
In note 1 Change the 
4 information guidance only. the following: 
Where a installation or 
appendix P must be 
word “guidance” to 
Reason: In New Zealand  part installation has 
complied with."
requirements. 
"Any RCD that forms part of the  the ESR prescribes 
been instal ed in 
Act 
Reason:
installation shall be selected 
standard low voltage, 
accordance with 
Then remove the word  The IEC requriements 
and instal ed to be combatible  not IEC 60038. 
AS/NZS3003, the 
Reason so that the 
‘Notes' to make the 
around mode 4 charging 
with the types of lead intended 
requirements of 
requriements for safety  clause substantive. 
have been dermaticely 
to be used within the 
2.6.3.3.1 do not apply.” 
with Evs become 
changed since this clause 
installation. Consideration shall 
mandatory
Reason: to ensure that  was put into the standard.  be applied for potential 
the NZ requirement for  These changes have seen 
pulsating and constant DC fault 
Reason: to ensure that 
EV charging safety is 
the safety for mode 4 
currents and waveform 
the facilitation of home 
mandatory. 
chargers been moved into 
distortion.” 
medical treatment set 
Information 
the product itsef rather then 
out in AS/NZS 3003 can 
on the final sub circut and 
Reason: To ensure RCDs in an 
be effectively 
these changes have been 
installation are not blinded by 
implemented without 
captured in S4. This also 
the presence of DC and they 
extra regulator burdon 
avoids any regulatroy burdon  maintain their safety function as 
from having to install, 
Official 
on hi power supplies, eg for  wel  as ensure that the correct 
what in this case is, 
boats or busses, that need  type of RCD for EV charging is 
redundant electrical 
to be designed from scratch. considered.
products.
the 
under 
Released 

1982
Act 
Information 
Official 
the 
Need to write the policy 
paper wording for Evs - 
removal of mode 4 
under 
requiremets. 
Released 