This is an HTML version of an attachment to the Official Information request 'WorkSafe Advice to MBIE on Removal of Clauses 2.3.2.1.2 (b) & (c) of AS/NZS3000:2018'.
AS/NZS 3000:2007: Electrical 
AS/NZS 3000:2018
installations (known as the 
Electrical installations - Known as the Australian/New Zealand Wiring Rules
Australian/New Zealand Wiring 
Rules): including Amendments 1 and 
2, subject to the following 
modifications:
1. In 4.5.2.3.2, change “warning sign
shall be installed” to “warning sign
shall be installed or fitted in
domestic installations but may be
omitted from all other installations”.
2. In 4.18.1(b) and (c), change “all
live (active and neutral) conductors”
to “all active conductors”.
3. Add a new paragraph to 4.18.2:
“In New Zealand, only electrical
equipment that is directly
associated with the gas supply may
be installed in the hazardous areas
of a domestic installation, shown in
figure 4.10.”
4. Replace 4.18.3 with “In New
Zealand, only electrical equipment
(including metering equipment) that
is directly associated with the gas
supply may be installed in the
exclusion zones of a domestic
ll
f

under the Official Information Act 1982
Released 

AS/NZS 3000:2018
Electrical installations - Known as the Australian/New Zealand Wiring Rules - Inculding Amendment 1, Amendment 2, and Amendment 3. 
1982
Act 
Information 
Official 
the 
under 
Released 

WorkSafe proposes a 12 month transition period 
 
1.Remove reference to clause 1.7.3 Equipment selecƟon
2. Change to: Remove reference to 2.3.2.1.2(b)(I)  and 
between the current Australian/New Zealand Rules 
2.3.2.1.2(c)
and the version included in this update
The reason for this is that the Electricity (Safety) Regulations 
prescribe an equipment regime, it is not appropriate for 
The reason for this is that there needs to be an ability to switch 
AS/NZS3000 to also prescribe an equipment regime for New 
the neutral and earth for EV charging and when an installation is 
Zealand.
operated independent of the grid.
1982
 
Act 
Information 
Official 
the 
under 
Released 

 
3.Delete clause 2.6.2.2.3(b) and replace it with:
 
4.Delete 2.6.3.3.2 ExcepƟon 2, Bullet point 2 – this 
 
5.In clause 4.18.5 ReƟculated 
 
6.Amend clause 4.18.5 so that the term "hazardous 
exception is no longer needed due to change in 
lighter-than-air gas system, delete  area" has the same meaning as "exclusion zone" and 
"Either type A in accordance with IEC 61009.1 or IEC 
technology use.
the words "lighter-than-air" 
the title for Figure 4.20.
61008.1 
Or
Reason: this would allow this 
Reason: A hazardous area is different to an exclusion 
Type F or Type  B in accordance with IEC 62423."
clause to also apply to reticulated  zone. An exclusion zone does not allow any electrical 
LPG installations.
equipmet into the zone where as a hazardous area, 
1982
which does not exist in residential, requires special 
This is to allow the use of Type B and F RCDs and also 
precaustion for eletrical equipment as well as a 
refer to the stnadard cited in Schedule 4.
periodic inspection. We do not want to impose a 
Act 
periodic inspection on domestic premesis in this 
way.
Information 
Official 
the 
under 
Released 

 
7.In clause 8.3.10 paragraph 2 delete the words "either by 
With the exception of clause 7.9.4
Clause 7.9.3 change title and all 
What are we doing about appendix 
the operation of the integral test device, or".
words in the clause to remove the  P? also add in all rcds to have a 
word “domestic” 
residual current rating of not 
Delete note 4.
Reason: to clarify that the clause  exceeding 30 ma.
applies in all installation rather 
Clause 8.3.10 add in new paragraph 5 after paragraph 4: 
than just domestic 
Add 7.9.3.4 The requirements in 
The function testing of the RCD is to include trip time, as well 
appendix P must be complied with.
1982
as confirmation that the functions that the RCD has are 
working, as well as confirmation that protection against 
electric shock is provided by which tripping is ensured for 
Act 
residual sinusoidal alternating current and residual pulsating 
direct current, as well as the presence of DC leakage and 
wave form distortion, as well as constant DC where 
applipable.”
The reason for this is to ensure that RCDs are tested to 
ensure that they are working but are not deemed unsafe by 
Regulation 24 of the Electricity (Safety) Regulations due to 
the trip time.
Information 
Official 
the 
under 
Released 

Change: 2.2.1.4 
Change clause 7.9 and appendix P to make all  Change clause 1.5.6.3: 
Delete clause 1.6.2(c) note (b)
Replace: 
Remove the title ‘Notes” and make the clause substantive. 
Mode 4 information guidance only.
At the end of paragraph 1 insert the 
2.6.3.3.3 – All with “ Where a 
(1) Change the word “guidance” to requirements. 
following: 
Reason: In New Zealand the ESR 
installation or part 
prescribes standard low voltage, not IEC  installation has been installed 
Reason: to ensure that the NZ requirement for EV charging is 
"Any RCD that forms part of the 
60038. 
in accordance with 
mandatory. 
installation shall be selected and 
AS/NZS3003, the 
installed to be compatible with the types 
requirements of 2.6.3.3.1 do 
1982
of lead intended to be used within the 
not apply.” 
installation. Consideration shall be 
applied for potential pulsating and 
Act 
constant DC fault currents and 
Reason: to ensure that the 
waveform distortion.” 
facilitation of home medical 
treatment set out in AS/NZS 
Reason: To ensure RCDs in an 
3003 can be effectively 
installation are not blinded by the 
implemented. 
presence of DC and they maintain their 
safety function. 
Information 
Official 
the 
under 
Released 

1982
Act 
Information 
Need to write the policy paper 
wording for Evs - removal of mode 
4 requiremets. Make the 
requirements mandatory
Official 
the 
under 
Released